Description
Benefits:
Low-GWP refrigerant R454B
Extended Range: There are 10 sizes available to meet any thermal load requirements up to 130 kW with a single unit;
Maximum versatility, with the ability to combine up to 6 modules for a total heat output of 780 kW.
Leaving hot water at up to +60°C;
The design is compact, measuring only 1 metre wide.
Technical Specifications:
Scroll compressors and Eco-Profile axial fans are statically and dynamically balanced.
Controlling condensing pressure through variation of fan speed;
Evaporator: stainless steel AISI 316 brazed plate type, externally insulated, with differential pressure switch and antifreeze protection electric heater.
Air-side heat exchanger: high efficiency finned coils with seamless copper tubes extended into corrugated aluminum.
Electronic expansion valve.
The microprocessor is housed in galvanized and painted steel plates.
Communication card: RS485
Options:
Hybrid smart coolingR (2-way modulating valve with brazed heat exchanger);
Power factor correction for cos phi 0.91;
Control panel for electric heater with thermostat.
Phase failure protection relay.
TP Serial card with BacNet Protocol (MS/TPXTCP/IP) and Gateway Modbus LonTalk™.
Low ambient temperature kit for cooling (-10 °C) and heat pump (-15 °C).
3-way valve for domestic hot water (DHW).
Eco-friendly electronic fans.
Soft-starter, automatic circuit breakers.
Eco-Profile Electronic Fans with High Head Pressure (100 Pa), Refrigerant Gauges, and Protection Grilles.
Special treatment for condenser coils.
Oversized water pump seal for use with glycol > 25%X > 40%;
Anti-freeze protection for hydraulic versions equipped with hydraulic kits.
Kits:
The sea container package includes a remote control display, flow switch, automatic water filling, strainers, water gauges, and rubber and spring anti-vibration mounts.
The following options and kits are required for the modular configuration:
The following items are required: – Multi-Manager System (mandatory); – Hydraulic connection kit for connecting single modules; – Victaulic clamps and caps (2 pcs for mounting on the unit manifold); – Victaulic clamps (2 pcs).
Versions:
Basic version: – H heat pump.
Energy version 1: – D Desuperheater (partial recovery).
Acoustic variants (1): – L Low noise (with compressor sound coats).– S Super low noise (with an improved sound jacket for compressors).
Hydraulic versions: (1):– B/M/A Hydraulic kit includes 1×2 pumps (ON-OFFXInverter operated), with low (B)Xhigh (A) available head pressure.
Hydraulic models with a water tank (1):– SB/SA, XB/XA. Hydraulic package includes N.1 (S)XN.2 (X) pumps (ON-OFFXInverter driven), with low (B)Xhigh (A) available head pressure, expansion vessel, and 120 liter buffer tank. (1) Will be mixed with basic versions.